Sustainable AI Group

Closed AI Emissions Calculation

Converting CLEER accelerator energy into greenhouse gas emissions for enterprise use of closed AI models
COMPANION TO CLEER TECHNICAL REPORT
↓ Download PDF
Cite this report
Suggested citation

Gamazaychikov, B., Jegham, N., & Luccioni, S. (2026). Closed AI Emissions Calculation: Converting CLEER accelerator energy into greenhouse gas emissions for enterprise use of closed AI models. Sustainable AI Group. Version CAIEC-0926. https://reports.sustainableaigroup.com/ai-emissions

BibTeX
@misc{saig2026caiec,
    title        = {Closed AI Emissions Calculation: Converting CLEER accelerator energy into greenhouse gas emissions for enterprise use of closed AI models},
    author       = {Gamazaychikov, Boris and Jegham, Nidhal and Luccioni, Sasha},
    howpublished = {Sustainable AI Group},
    year         = {2026},
    month        = sep,
    note         = {Version CAIEC-0926},
    url          = {https://reports.sustainableaigroup.com/ai-emissions}
  }
By Boris Gamazaychikov, Nidhal Jegham, and Sasha Luccioni
VERSION
CAIEC-0926
DATE
29 SEPTEMBER 2026

1. Introduction

The CLEER Technical Report estimates the accelerator energy consumed per input and output token by closed AI models (Jegham et al. 2026). This document converts those estimates into greenhouse gas (GHG) emissions suitable for inclusion in a corporate inventory.

The methodology builds on existing accounting standards and published evidence. However, studies of AI emissions currently differ in their system boundaries, functional units and disclosure practices (Kim et al. 2026); introducing another stand-alone accounting method would add to this fragmentation. We therefore use established frameworks to define the accounting boundary and draw on published measurements to quantify the emissions within it:

  • The GHG Protocol Scope 3 Standard defines the accounting boundary and allocation rules (GHG Protocol 2011), while its Scope 2 Guidance governs electricity accounting (Greenhouse Gas Protocol 2015).
  • ITU-T L.1801 provides cut-off rules and functional units (ITU-T L.1801 2026).
  • The Green Software Foundation’s SCI for AI, which extends ISO/IEC 21031:2024, establishes a consumer-side boundary for inference and uses tokens as the functional unit for language models. Our inference footprint follows this boundary (Green Software Foundation 2025).
  • Host, facility and hardware factors draw on Google’s production telemetry and life-cycle assessments (Google 2025; Schneider et al. 2025) and NVIDIA’s ISO 14067 product carbon footprints (NVIDIA 2025), with each checked against independent measurements.
  • The calculation follows the overall structure of Watershed’s activity-based AI emissions framework, which identifies model-specific energy per token as its principal missing input (Watershed 2026).

Where sources agree, we adopt their shared estimate; where they differ, we document the range and include it in the uncertainty analysis.

The existing sources span AI hardware measurements, life-cycle assessment, data center engineering, energy systems and methane research, analyses of AI company compute spending, and carbon accounting standards. Overall, we reviewed more than 40 sources against their underlying primary data (Annex E).

Existing frameworks establish which emissions to account for, but provide few of the numerical inputs needed to estimate them for closed models. This document quantifies each factor, identifies its source and assesses the likely direction of error. The resulting calculation can be reproduced from token counts through to reported emissions, with individual factors replaced as providers release better data.

We note that AI emissions accounting remains an emerging field: serving architectures and provider disclosures evolve faster than the published research, and the evidence supporting some factors remains limited. We identify these limitations where they arise and will update the calculation as better data becomes available. All factor changes will be recorded publicly. Feedback, corrections and additional data are welcome through the public repository.

1.1 Accounting Problem

Companies purchasing access to hosted AI models generally have limited visibility into the infrastructure serving their requests. They typically cannot determine:

  • which data center processed a request;
  • the hardware configuration used;
  • how much electricity was consumed or how it was procured;
  • the energy attributable to an individual request.

Even without these disclosures, companies need a defensible basis for estimating the associated Scope 3 emissions (GHG Protocol 2011).

Our calculation uses activity data that companies can substantiate themselves. It converts usage into token counts and applies each model’s estimated accelerator energy intensity. Additional factors account for:

  • host equipment;
  • idle capacity;
  • facility overhead;
  • electricity carbon intensity;
  • hardware manufacturing;
  • data center construction;
  • the provider’s model development.

Each material factor is documented alongside its source, evidence base, methodological status and known direction of uncertainty.

1.2 Relationship to the CLEER Technical Report

These two documents meet at the estimate of per-token accelerator energy. The CLEER Technical Report develops this estimate for closed models through a sequence of modelling, benchmarking and validation steps (Jegham et al. 2026):

  • Pruning open mixture-of-experts models to retain the components active during production inference.
  • Benchmarking the resulting models across expert parallelism configurations and batch sizes.
  • Validating benchmark results against published deployment data.
  • Matching closed models to comparable open models.
  • Using published latency figures to estimate accelerator power and energy per token.

This document takes CLEER’s per-token accelerator energy estimates as inputs without repeating their derivation. Section 4 defines the handoff between the 2 methodologies, including the quantities supplied by CLEER, their system boundary and associated uncertainty, and the checks used to prevent double-counting in subsequent stages of the emissions calculation.

1.3 Calculation Chain

The calculation starts with the number and type of tokens a company uses with each named model. CLEER estimates the accelerator electricity needed to serve those tokens. For a corporate inventory, this report also allocates a share of the provider’s model-development energy to that use.

The serving and development estimates are carried separately through the electricity calculation. Both include the energy used by surrounding server equipment and the data center. Capacity kept ready to answer requests is added only to serving, because development work does not require the same reserve.

Facility electricity is then converted into operational greenhouse gas emissions. Emissions from manufacturing IT equipment and constructing data centers are added to produce the reported inventory footprint. The figure summarizes this sequence; §10.1 gives the full equations.

Figure 1: Calculation chain from customer token activity through serving and model-development energy to the reported greenhouse gas inventory footprint.

1.4 Adopted Factors

The table below lists the central factors used at each stage of the calculation. Later sections explain their evidence and uncertainty.

Table 1: Adopted factors. Values apply to the central calculation; sensitivities are reported in §11.
Factor GPU-served TPU-served Basis §
Accelerator energy per token CLEER, by model CLEER, by model Modelled 4
Cached-input intensity r(m) × input intensity r(m) × input intensity Proxy, provider price ratio 4.2
Host uplift, h ×1.50 ×1.43 Measured and published system data 5.2
Idle and provisioned capacity, i ×1.10 ×1.10 Production measurement 5.3
Power usage effectiveness, p ×1.45 ×1.45 Default proxy 5.4
Combined serving uplift, h × i × p ×2.39 ×2.28 Calculated 5.5
Grid carbon intensity, CI 0.41 kgCO₂e/kWh 0.41 kgCO₂e/kWh US lifecycle average 6
Behind-the-meter override 0.64 kgCO₂e/kWh 0.64 kgCO₂e/kWh Modelled lifecycle gas generation 6.4
Embodied IT intensity, I_emb 90 gCO₂e/kWh 145 gCO₂e/kWh Per kWh of accelerator energy 7
Data center construction, k_c 7 gCO₂e/kWh 7 gCO₂e/kWh Per kWh of facility electricity 8
Model-development ratio, d 1.5 1.5 Sector-level proxy 9

1.5 AI Terms in GHG Accounting Language

Table 2: AI terms and their GHG accounting analogues.
AI term Definition GHG accounting analogue
Token Unit of text processed by a model, approximately 3.5–4 characters of English text Activity-data unit
Input or prompt token Text supplied to the model Activity data
Output or completion token Text generated by the model Activity data; typically more energy-intensive than input
Cached input token Previously processed input reused by the serving system Activity data with reduced estimated intensity (§4.2)
Per-token energy intensity Accelerator electricity consumed per token for a named model, in Wh/token Pre-carbon energy factor
Inference Operation of a trained model to answer a request Activity being accounted for
Model development Compute used to create and improve models, including training, post-training, experiments, unreleased runs and research Supplier activity allocated to customer output (§9)
Closed model Model for which weights and serving configuration are not publicly available Supplier activity for which primary operational data are unavailable
Accelerator Specialized processor used for AI computation, including GPU, TPU and wafer-scale systems Primary energy-consuming IT asset
Batch size Number of requests processed concurrently by an accelerator Serving load factor
Serving fleet Machines provisioned to provide inference Basis for idle-capacity treatment
Routing layer Software that dispatches requests among multiple models Attribution layer; emissions are assigned to underlying models

1.6 Evidence Basis

The calculation draws on published evidence assessed against primary sources (Annex E) and on SAIG’s own empirical work, comprising the CLEER benchmarking campaign and the host-power measurements in §5.2 and Annex B. Its alignment with applicable accounting frameworks is set out in Annex C.

Where independent evidence converges, the calculation adopts the convergent value and records the supporting sources. Where credible evidence diverges, it documents the range, selects a value with a stated rationale and carries the unresolved difference into the uncertainty treatment in §11 where material. Where adequate published evidence is unavailable, direct measurement is used where feasible. Remaining gaps are treated as assumptions, proxies or limitations and disclosed accordingly.

2. Scope and Boundary

2.1 Intended User and Services Covered

The calculation applies to an organization that uses generative AI services operated by a third party, through a vendor application, API or routing layer. The customer does not develop or operate the underlying model and has no operational control over the infrastructure used for inference. Request-level data on rack power, facility power usage effectiveness (PUE), serving location and electricity supply are assumed to be unavailable from the provider. The data hierarchies and fallback factors in later sections address this constraint.

Models trained, fine-tuned or self-hosted by the customer are out of scope. Those activities are under the customer’s operational control and belong in the applicable cloud, data center and corporate inventory methods.

Version 0926 of the calculation covers text inference, with tokens as the functional unit. The system boundary, uplift factors, embodied-emissions treatment and energy-to-carbon conversion also apply to other modalities, but the accelerator-energy factor is modality-specific– image, video and audio are future extensions.

2.2 Hardware Classes

Factors that vary by serving hardware are assigned to a hardware class: TPU-served refers to Google models served on Tensor Processing Units, which are Google’s proprietary accelerators used in their data centers. GPU-served refers to models served on NVIDIA Graphics Processing Units and is the default classification unless evidence supports another class. Hardware outside these classes is treated under §5.6.

2.3 Included Sources

Table 3: Sources included in the system boundary.
Component Treatment §
Serving accelerator energy CLEER estimate per token and model (Jegham et al. 2026) 4
Host CPU, DRAM, NICs, storage, fans and PSU losses ×1.50 GPU-served; ×1.43 TPU-served (Google 2025; Latif et al. 2025; NVIDIA DGX H100 System Specification 2023) 5.2
Idle and provisioned capacity ×1.10; serving energy only (Google 2025; Oviedo et al. 2026) 5.3
Facility overhead PUE; default 1.45 (Watershed 2026; Shehabi et al. 2024) 5.4
Model development Development ratio d applied to serving accelerator energy 9
Embodied IT hardware Accelerator, host tray and distribution, amortized 7
Data center construction 7 gCO₂e/kWh of facility electricity (Schneider et al. 2025) 8

2.4 Excluded Sources

A source may be excluded on materiality only where its contribution is estimated to be below 1% of operational serving emissions and the cumulative effect of all excluded sources also remains below 1% (ITU-T L.1801 2026; Carbon Trust 2026). ITU-T L.1801 adopts the cut-off principles of ITU-T L.1410, including consideration of mass, energy, environmental significance and the cumulative effect of excluded processes (ITU-T L.1801 2026). The 1% source-level threshold is more restrictive than the 5% threshold commonly applied to corporate Scope 3 line items and is consistent with the Carbon Trust precedent (GHG Protocol 2011; Carbon Trust 2026).

Table 4: Sources excluded from the system boundary. Derivations are in Annex A.
Source Estimated bound Treatment
Downstream data storage ~0.11% at 1-year retention (Nibler and Ropars 2025; Google 2025) Excluded below materiality threshold
External network transmission ~0.43% at 2020 intensity; ~0.17% at 2025 intensity (Coroamă 2021; IO 2026; Mytton et al. 2024) Excluded below materiality threshold
End-user devices Not additive Excluded to prevent double-counting in the customer’s inventory
Hardware end-of-life ~0.12–0.17% location-based; ~0.38% market-based (Falk et al. 2026; Schneider et al. 2025; Mistral AI et al. 2025) Excluded below materiality threshold
Total quantified ~0.71% location-based; ~0.92% market-based Below the 1% aggregate cut-off
ImportantKey finding

The quantified exclusions sum to approximately 0.71% of operational serving emissions on a location-based basis and 0.92% on a market-based basis. Both remain below the 1% aggregate cut-off. Data center construction (§8) and hardware distribution (§7.2) exceed the source-level threshold and are included.

3. Activity Data and Model Coverage

3.1 Activity Data

The calculation requires uncached input, cached input and output token counts by model:

\[T_{\mathrm{in}}(m),\ T_c(m),\ T_{\mathrm{out}}(m)=\sum \text{activity attributable to model }m\]

The preferred source is provider or customer telemetry that reports token counts directly, treated as measured activity data. Many enterprise AI tools do not expose token-level usage and report prompts, messages, conversations, active users, sessions, credits or billed work units instead. In these cases, activity is converted to tokens, or directly to accelerator energy, using a documented estimation method based on the most specific data available.

Table 5: Activity-data hierarchy.
Rung Basis
1 Direct token telemetry by model
2 Token telemetry covering part of the reporting period, extended using a related usage driver available for the full period
3 Non-token usage telemetry converted to tokens with an evidenced tokens-per-unit relationship
4 Bundled or product-specific usage units converted directly to accelerator energy with a documented physical or empirical relationship
5 Reference workload or proxy data from an appropriate external dataset

Spend-based estimates are used only where no physical activity measure can reasonably be obtained. Public workload datasets (e.g., conversation logs, production traces, agentic workflows) provide reference workloads and are not direct measurements of a particular customer’s activity.

3.2 Estimating Incomplete Activity

Each estimate documents the observable starting unit, the conversion relationship, the measured and estimated shares of activity, the source of any workload assumptions and the principal direction of uncertainty.

The arithmetic mean is used when converting activity units into a period total. Ratios used in a conversion, such as tokens per unit of activity or the cached share of input, are calculated as total over total, not as an average of per-request or per-user ratios. Chat and agentic reference datasets show substantial differences between representative and mean workloads, and median values understate totals for right-skewed usage.

Where the observable unit is a user-visible action, tokens per unit reflect everything sent to and generated by the model for that action, which may include accumulated conversation context, hidden system prompts, reasoning tokens and sub-agent requests. These components are included where reported or supported by an appropriate dataset, and are not added where reported token counts already contain them. Unsupported multipliers are not introduced to make an estimate more conservative.

3.3 Model Assignment

Activity is assigned to the model that served it where that information is available. Otherwise, assignment uses the best available evidence, which may include provider documentation, model-availability dates, known default changes, product configuration or observed model-tier information. An optional model announcement alone is not evidence that the model has become the default for all users. Where a service routes requests across several models and the routing mix is not reported, a documented proxy covers only the models available during the reporting period.

Where cache-hit telemetry is available, cached and uncached input tokens are separated. Otherwise caching follows §4.2. Cache behavior is workload- and provider-specific: a cache rate derived from an agentic workflow is not applied automatically to ordinary chat usage, and cache reuse inferred from repeated content is an upper bound, since cached entries expire between requests.

3.4 Model Coverage and Long-Tail Fallback

The calculation targets named-model coverage of at least 99.9% of token volume in each reporting period. Corporate AI usage often includes a long tail of models used for testing, evaluation or limited trials that together account for a very small share of volume. The 99.9% threshold is a methodological choice, not derived from an external standard, intended to limit the share of activity that depends on a generic factor.

Residual activity that cannot be matched to a named CLEER factor is assigned the highest-intensity CLEER-covered model within the same provider and tier, or, where provider or tier is unknown, the highest-intensity model in the current CLEER factor set. The fallback is a conservative bound for a small residual share, not an estimate of the unmatched model. Named-model coverage is disclosed for each reporting period.

4. Accelerator Energy

4.1 CLEER Output

CLEER estimates accelerator energy per token for a named model, with separate mean and standard-deviation values for input and output tokens (Jegham et al. 2026). It covers accelerator energy only. Host CPU and DRAM, other server components, provisioned idle capacity, facility overhead and carbon conversion are added separately in §§5–6.

For model m:

\[E_{\mathrm{acc}}(m)=T_{\mathrm{in}}(m)\bar e_{\mathrm{in}}(m)+T_c(m)r(m)\bar e_{\mathrm{in}}(m)+T_{\mathrm{out}}(m)\bar e_{\mathrm{out}}(m)\]

Inputs and outputs are calculated separately because their energy intensities differ: input is processed through parallelized prefill, whereas output is generated sequentially through decode and is generally more energy-intensive per token.

4.2 Cached Input Tokens

A cache hit reuses key-value states generated by a previous request. This avoids part of the prefill computation, but the cached state must still be read from accelerator memory and remains part of decode-time attention, so cached input has a non-zero energy intensity.

Cache-hit energy cannot be measured for closed models because the serving implementation is not observable. The calculation uses the provider’s published cache-read price ratio, r(m), as a proxy for the reduction in accelerator intensity:

\[\bar e_{\mathrm{in}}(\mathrm{cached},m)=r(m)\bar e_{\mathrm{in}}(m)\]

Cache-hit prices reported by Artificial Analysis imply cache-read-to-standard-input ratios from 0.10 to 0.50 across reviewed models (Artificial Analysis 2026). Because the ratio is a price proxy and not a physical measurement, it is classified as proxy data and its direction of error is not established.

A cache write does not avoid the initial prefill computation. Cache-write tokens are treated as ordinary uncached input at ēᵢₙ(m). Where telemetry does not distinguish cache writes from uncached input, no adjustment is required.

4.3 TPU-Served Models

Google does not make TPU power telemetry available through an equivalent of NVIDIA’s System Management Interface (nvidia-smi), which CLEER uses to measure GPU power during benchmarking. CLEER therefore estimates Gemini accelerator energy from Google’s published accelerator-energy disclosure and documented TPU hardware characteristics. This derivation is documented in Appendix A of the CLEER Technical Report (Jegham et al. 2026).

4.4 Reasoning Modes

Reasoning levels of the same model are not treated as separate models - reasoning level changes the amount of generation permitted rather than the per-token energy intensity of a distinct model, so additional reasoning increases emissions through the output token count, Tₒᵤₜ, rather than through a separate ēₒᵤₜ. Where provider telemetry already includes reasoning tokens within completion tokens, no additional reasoning multiplier is applied.

5. Facility Energy

This section converts serving accelerator energy into the electricity drawn at the facility boundary:

\[E_{\mathrm{fac}}=E_{\mathrm{acc}}hip\]

where h is host uplift, i is idle and provisioned-capacity uplift and p is PUE. Each factor represents a separate physical component of the system boundary. Including host power alongside accelerator power follows established practice in AI energy measurement (Strubell et al. 2019; Luccioni et al. 2024).

5.1 Evidence for Non-Accelerator Power

Table 6: Evidence for non-accelerator power and implied host multipliers.
Source Evidence basis Implied multiplier
Google Gemini production fleet 0.14 Wh active accelerators and 0.06 Wh host CPU and DRAM per median prompt (Google 2025) ×1.43
Metered 8-GPU H100 HGX node 7.9–8.4 kW node power against 5.6 kW tray TDP under training load (Latif et al. 2025) ×1.41–1.50
GB200 reference architecture Published server and accelerator specifications (Epoch AI 2025a) ×1.53
NVIDIA DGX H100 10.2 kW rated ceiling against 5.6 kW tray (NVIDIA DGX H100 System Specification 2023) ×1.82 nameplate
Google TPU fleet, five generations Measured mean machine power relative to measured accelerator power over six years, all workloads (Schneider et al. 2025) ×1.64–2.22; mean 1.88

The adopted GPU host factor is based primarily on production and physically metered evidence. Nameplate values are retained as sensitivity bounds because they describe maximum configured power rather than normal operating power. The TPU fleet ratios cover all workloads and all hours, including host activity during low accelerator load, so the Gemini-specific serving measurement is adopted for TPU-served models.

The metered H100 range reflects accelerators operating at or near their 700 W TDP (Latif et al. 2025; NVIDIA DGX H100 System Specification 2023). SAIG benchmarking indicates that this does not hold in serving: eight-accelerator H200 configurations averaged approximately 57% of TDP during active serving (Annex B). Accelerator draw below TDP raises the implied non-accelerator multiplier, so the adopted GPU factor is more likely to understate than overstate host energy.

Google reports data center networking as negligible for a median text prompt (Google 2025). Other studies estimate central networking at approximately ×1.10 to ×1.14 above server power for relevant architectures (Oviedo et al. 2026; Epoch AI 2025a; Choukse et al. 2025). No networking uplift is applied in the central calculation; ×1.14 is retained as an upper sensitivity in §11.

Google reports 0.24 Wh per median prompt under its comprehensive boundary and 0.10 Wh under a narrower approach that counts active accelerators only and samples the most efficient 10% of data centers (Google 2025). The ×2.4 ratio between them combines two effects:

\[\begin{aligned}\text{Boundary uplift}&=0.24/0.14=1.71\\\text{Facility-sample effect}&=0.14/0.10=1.40\\\text{Combined}&=2.40\end{aligned}\]

The uplift chain in this section is compared with the ×1.71 boundary uplift. The facility-sample effect is addressed through the PUE treatment in §5.4 and is not added again as a separate multiplier.

5.2 Host Uplift

RAPL telemetry from an eight-accelerator B300 node measures combined CPU package and DRAM power at approximately 375 W, with a coefficient of variation of 3.6% across 60 runs covering 4 models and batch sizes of 32–384 (Annex B). The term behaves as an approximately constant offset and does not vary materially with batch size. Its implied multiplier is:

\[h_{\mathrm{cd}}=1+\frac{P_{\mathrm{host}}}{N_{\mathrm{acc}}\bar P_{\mathrm{acc}}}\]

At eight accelerators, h_cd is approximately ×1.04–1.07 at accelerator TDP and ×1.09–1.12 at measured average serving power (Annex B). This component is measured, and its application to H200 and B200 assumes a comparable host platform.

CPU and DRAM do not represent the full host boundary; NICs, PSU losses, fans, storage and chassis power remain. Latif et al. report node power of ×1.41–1.50 of tray TDP under training load (Latif et al. 2025). Removing the CPU and DRAM component at H100 TDP (×1.07) leaves ×1.32–1.41 for the remaining components; the GB200 reference architecture implies ×1.43 (Epoch AI 2025a). The adopted remainder is the Latif midpoint, ×1.36, a calculated proxy based on published system measurements. The combined GPU host factor is:

\[h\approx 1.10\times1.36=1.50\]

At measured serving power, the product is approximately ×1.48–1.52 across the three benchmarked accelerator classes. A published processor-telemetry figure near ×1.08–1.11 is not a complete host uplift unless its measurement boundary also includes the remaining server components.

5.3 Idle and Provisioned Capacity

Serving fleets hold capacity ready to meet latency requirements. Google reports provisioned idle machines at 0.02 Wh against 0.20 Wh of active accelerator and host energy per median prompt, an uplift of ×1.10 (Google 2025). Oviedo et al. model a range of ×1.05 for highly utilized fleets to ×1.20 for low-utilization fleets (Oviedo et al. 2026). The present calculation adopts ×1.10 and applies it to serving energy only. CLEER’s batch-size treatment applies within active serving; the idle factor covers machines that are provisioned but not actively serving.

5.4 Power Usage Effectiveness

PUE is the ratio of total facility electricity to IT equipment electricity.

Table 7: Hierarchy for selecting the PUE factor.
Rung Basis
1 Facility-specific PUE where both serving site and site PUE are disclosed
2 Provider fleet-average PUE where the disclosure demonstrably covers the capacity serving the workload
3 1.45, the US average applied in Watershed’s open AI emissions framework, derived from LBNL (2024) Figure 4.6 (Watershed 2026; Shehabi et al. 2024)

If a provider can specify the region/site serving the AI workload, that specific site’s PUE shall be used (rung 1). If a provider does not share this information but can guarantee that the workload is served only on first-party data centers, provider fleet-average PUE shall be used (rung 2). However, public evidence1 exists connecting every hyperscaler to third-party data center providers (e.g. neoclouds).

Hyperscaler fleet-average PUE values do not include third-party data centers. Therefore, no current provider disclosure is treated as satisfying rung 2, because providers may use contracted third-party capacity outside their reported owned-facility fleets. Due to this situation, rung 3 is the likely scenario unless rung 1 is satisfied.

The value of 1.45 is a proxy, not a measurement of the serving facility2. Documented scenarios are 1.09 for Google’s measured fleet (Google 2025), 1.20 for a purpose-built AI facility (Oviedo et al. 2026) and 1.56 for the global data center average (Uptime Institute 2024). The 1.09 scenario reduces the serving chain by approximately 25%.

5.5 Adopted Factors

Table 8: Adopted factors for converting accelerator energy to facility energy.
Factor Adopted value Status
GPU host uplift ×1.50 Measured CPU and DRAM component plus documented platform remainder
TPU host uplift ×1.43 First-party production measurement
Idle and provisioned capacity ×1.10 Production measurement with independent corroboration
PUE ×1.45 Default proxy
Combined GPU serving uplift ×2.39 Calculated
Combined TPU serving uplift ×2.28 Calculated

With Google’s own measured PUE, the TPU chain reproduces Google’s reported boundary uplift within rounding:

\[1.43\times1.10\times1.09=1.71\]

The central calculation uses the higher default PUE because serving-facility attribution is unavailable.

ImportantKey finding

The adopted host, idle-capacity and PUE factors expand accelerator energy to facility energy by ×2.39 for GPU-served models and ×2.28 for TPU-served models.

5.6 Hardware Outside the Benchmarked Classes

Where serving hardware does not map to the GPU or TPU classes, the GPU token chain is not applied automatically. The energy of the vendor’s billing unit is estimated from hardware-specific evidence, with accelerator inference, sandbox compute, orchestration and storage each assigned factors appropriate to their own hardware boundaries. The estimate is triangulated against a second method based on different evidence such as capacity occupancy, task-level measurements or billing economics. Right-skewed inputs use the percentile treatment in §11.1, and the record identifies the dominant unmeasured input and the provider disclosure that would replace it. A published overhead measurement that covers processor telemetry only is treated as a lower bound for full host overhead.

6. Electricity Carbon Intensity

Request-level serving location and electricity supply are generally unavailable to the customer – the calculation therefore applies an explicit data hierarchy. A higher rung is used where the required evidence is available, and the applicable rung is recorded by the provider.

6.1 Data Hierarchy

Table 9: Hierarchy for selecting the electricity carbon-intensity factor.
Rung Basis
1. Preferred Region-specific grid factor where serving region is disclosed
2. Fallback Provider-disclosed fleet-average emissions factor
3. Default 0.41 kgCO₂e/kWh lifecycle: eGRID2024 US national CO₂e total output rate plus upstream fuel supply (Cornerstone Sustainability Data Initiative 2026; Alvarez et al. 2018)
4. Behind-the-meter override 0.64 kgCO₂e/kWh lifecycle natural-gas generation, blended across the US behind-the-meter technology mix, where documented exposure exists and actual generation data are unavailable (Holbrook et al. 2026; O’Donoughue et al. 2014; Alvarez et al. 2018)

6.2 Location-Based and Market-Based Reporting

Both location-based and market-based emissions are reported. Location-based emissions are the primary inventory result because workload-level market-based electricity attributes cannot normally be verified for closed-model inference. Where the customer cannot evidence contractual electricity attributes that meet the Scope 2 quality criteria, the market-based figure equals the location-based figure and the reason is disclosed (Greenhouse Gas Protocol 2015). General provider renewable-energy claims do not reduce the market-based factor unless the relevant contractual instruments can be attributed to the customer’s workload.

6.3 Default Grid Factor

All factors are stated on a lifecycle basis. The customer reports these emissions under Scope 3 Category 1, which covers the cradle-to-gate emissions of a purchased service. Upstream emissions of US grid electricity exceed the 1% threshold in §2.4 and are included.

Grid factors at rungs 1 to 3 have two components: the generation component is the eGRID CO₂e total output rate for the applicable region, and the upstream component is the fossil heat input per MWh of net generation in that region, derived from eGRID fuel-specific output and input emission rates and resource mix, multiplied by a fuel-specific upstream intensity. Natural gas uses 16.7 kgCO₂e/GJ, an author calculation combining supply-chain methane at the 2.3% leakage rate (Alvarez et al. 2018), converted at the AR6 GWP100 value (Forster et al. 2021), with non-methane upstream emissions (Argonne National Laboratory 2025). Coal uses 6.0 kgCO₂e/GJ and oil 12.0 kgCO₂e/GJ (Argonne National Laboratory 2025). Upstream emissions of non-fossil generation are below the §2.4 threshold and are excluded.

Applied to eGRID2024 national data, fossil heat input is 3.47 GJ/MWh of gas, 1.72 GJ/MWh of coal and 0.06 GJ/MWh of oil. The upstream component is 0.069 kgCO₂e/kWh and the rung-3 default is:

\[CI=0.341_{\text{generation}}+0.069_{\text{upstream}}=0.41\ \mathrm{kgCO_2e/kWh}\]

The generation component is the eGRID2024 US national CO₂e output rate, reconstructed using EPA’s published eGRID methodology and 2024 inputs (Cornerstone Sustainability Data Initiative 2026). Transmission and distribution losses are not added, as large data centers connect at transmission voltage, where losses are below the grid-average rate; this is a simplifying assumption. US data centers are disproportionately located in regions with above-average grid carbon intensity, so the national default may understate actual serving emissions (Guidi et al. 2024).

6.4 Behind-the-Meter Generation

A grid-average factor is not representative where the electricity serving a facility is generated on site or through an equivalent dedicated arrangement, a situation that is increasingly common3 for most AI providers. Rung 4 applies where credible public evidence documents provider exposure to behind-the-meter gas generation and the provider does not disclose actual generation data (Climate Power and Cleanview 2026). The trigger may be supported by air permits, interconnection filings, utility filings, equipment procurement records, local reporting or other credible public evidence.

The share of provider load served behind the meter is not inferred. Where exposure is documented and no load share is available, rung 4 is applied unblended at provider level as the conservative fallback. Because conservatism is applied at this step, the rung-4 factor is set as a central estimate, not an upper bound.

The factor includes combustion CO₂, combustion CH₄ and N₂O, upstream methane leakage, other upstream supply chain emissions and plant infrastructure. Methane and nitrous oxide are converted using 100-year global warming potentials from the IPCC Sixth Assessment Report (CH₄ 29.8, N₂O 273), the basis required by the GHG Protocol (Forster et al. 2021; World Resources Institute and World Business Council for Sustainable Development 2015).

Heat rates are derived from rated manufacturer efficiencies on a lower heating value (LHV) basis and converted to higher heating value (LHV/HHV = 0.901). Combustion CO₂ is 53.06 kgCO₂/MMBtu (US Environmental Protection Agency 2025). Combustion CH₄ and N₂O for turbines, and methane slip from lean-burn reciprocating engines, follow EPA AP-42 Tables 3.1-2a and 3.2-2 (US Environmental Protection Agency 2000). Upstream methane is calculated at the measured national supply chain leakage rate of 2.3% (Alvarez et al. 2018). Other upstream emissions are calibrated so that a combustion turbine at 33% HHV efficiency and 1.3% leakage reproduces the harmonized lifecycle median of 670 gCO₂e/kWh (O’Donoughue et al. 2014).

The factor is blended across the technology mix of binding behind-the-meter generation orders for US AI data centers, approximately 75 GW as of Q3 2026. Steam turbines are treated as the bottoming cycle of combined-cycle blocks, and undisclosed capacity is assigned the fleet average (Holbrook et al. 2026).

Table 10: Behind-the-meter technology mix and emission factors.
Technology LHV efficiency Emission factor kgCO₂e/kWh Share of generation
Gas turbines, simple cycle 38% 0.70 35.3%
Reciprocating engines 45% 0.73 32.3%
Combined cycle (gas turbine and steam) 55% 0.49 26.0%
Solid oxide fuel cells 54% 0.49 5.1%
Other or undisclosed Fleet average 0.64 1.3%
Fleet blended — 0.64 100.0%

The same method applied to a combustion turbine at 33% HHV efficiency yields 0.73 kgCO₂e/kWh at 2.3% leakage, consistent with the leakage-adjusted harmonized estimate. The difference between the two factors reflects the higher-efficiency combined-cycle and fuel cell capacity in the current behind-the-meter mix.

At the EPA inventory-implied leakage rate of 1.4%, the factor is 0.60 kgCO₂e/kWh (Alvarez et al. 2018). At the 2.43% weighted average from aerial measurement of six US production regions, it is 0.65 kgCO₂e/kWh (Sherwin et al. 2024). At 3.7% Permian Basin leakage, it is 0.71 kgCO₂e/kWh (Zhang et al. 2020). Excluding reciprocating engine methane slip reduces the factor to 0.60 kgCO₂e/kWh. On a 20-year GWP basis, reported for context only, the factor is 0.92 kgCO₂e/kWh.

Rated efficiencies are used because they are published and verifiable. Islanded plants hold spinning reserves and follow rapid AI load fluctuations, which lowers operating efficiency below rated values (Holbrook et al. 2026). A 5% relative efficiency loss would raise the factor to 0.68 kgCO₂e/kWh, so the adopted factor is more likely to understate than overstate operating emissions. The 0.64 kgCO₂e/kWh factor is a modelled proxy, not provider-specific measured generation data, and is replaced where a provider discloses verifiable generation data. Technology weights are updated as the behind-the-meter order book and operating fleet evolve.

7. Embodied Carbon of IT Hardware

This section estimates emissions from manufacturing and distributing serving hardware and allocates them over the hardware’s operating life. Embodied hardware emissions are included because reviewed life-cycle studies place them well above the 1% materiality threshold; for instance, Mistral’s production-model LCA reports hardware embodied emissions at approximately 11% of lifecycle GHG emissions (Mistral AI et al. 2025).

7.1 Accelerator Manufacturing

NVIDIA’s ISO 14067 product carbon footprints are the primary source for GPU hardware (NVIDIA 2025).

Table 11: NVIDIA accelerator-baseboard product carbon footprints.
Baseboard Cradle-to-gate footprint Per accelerator
HGX H100, 8 × H100 SXM 1,312 kgCO₂e 164 kgCO₂e
HGX B200, 8 × B200 SXM6 2,274 kgCO₂e 284 kgCO₂e

The H100 footprint is the base GPU factor: independent A100 studies report approximately 141–143 kgCO₂e per card and corroborate the general magnitude (Falk et al. 2026; Lees-Perasso et al. 2026). A separate ADEME parametric estimate for H100s produces approximately 235 kgCO₂e per card, around 43% above NVIDIA’s value despite a narrower boundary; the divergence is attributed principally to background database selection (Lees-Perasso et al. 2026). No adjustment is made to the NVIDIA footprint because it has the stronger review and primary-data provenance, but the divergence is retained as a systematic uncertainty in §11.

For TPU-served hardware, Google’s TPU life-cycle assessment reports manufacturing and transport emissions for complete machines (Schneider et al. 2025). The calculation uses TPU v6e (Trillium), the generation CLEER assumes for Gemini serving (Jegham et al. 2026): 583 kgCO₂e per TPU over the machine, of which 323 kgCO₂e is the TPU tray and 260 kgCO₂e the host share, or 4,664 kgCO₂e for an eight-TPU machine including transport.

7.2 Boundary Adjustments

Host Tray

The NVIDIA footprint covers the accelerator baseboard but not the complete serving machine, which also includes CPUs, system DRAM, storage, chassis, PSUs and fans.

Table 12: Evidence for the share of full-machine embodied emissions attributable to host components.
Evidence Host share
Google TPU v5e machine 34.4% (Schneider et al. 2025)
Google TPU v6e machine 44.6% (Schneider et al. 2025)
Boavizta/EcoLogits 8 × A100 server 72.4% (GenAI Impact and Boavizta 2025)
EcoServe ~75% (Li et al. 2025)

The GPU factor adopts the Boavizta value of 72.4%, a host-tray uplift of ×3.62. EcoServe’s approximately 75% would raise GPU embodied intensity by approximately 10% and falls within the uncertainty carried in §11. The TPU v6e machine total already includes its host tray (×1.80 over the TPU tray alone).

Distribution

The NVIDIA footprint is cradle-to-gate and excludes the shipment of finished hardware to the data center. Published estimates imply a distribution uplift of approximately ×1.06–1.21, depending on hardware and transport assumptions (Schneider et al. 2025; Falk et al. 2026; Lees-Perasso et al. 2026). The calculation adopts the rounded midpoint of ×1.12 for GPU-served hardware. Distribution is already included in the Google TPU total.

7.3 Amortization

Embodied machine carbon is converted to an intensity per kWh of accelerator energy, the form that applies directly to CLEER output, by dividing by lifetime accelerator energy:

\[I_{\mathrm{emb}}=\frac{M}{L\times 8{,}760\times\bar P_{\mathrm{acc}}}\]

where M is embodied emissions per serving machine, L is service life in years and P̄_acc is the machine’s average accelerator power over its installed life, including active serving and provisioned-but-idle periods.

Table 13: Embodied-hardware calculation stack and resulting intensity.
Step GPU-served TPU-served
Accelerator baseboard or tray 1,312 kgCO₂e (HGX H100) 2,584 kgCO₂e (8 × TPU v6e)
Host-tray uplift ×3.62 ×1.80
Distribution ×1.12 Included
Embodied carbon per machine, M ≈5,325 kgCO₂e ≈4,664 kgCO₂e
Average accelerator power, P̄_acc 2.24 kW (40% of 5.6 kW tray TDP) 1.22 kW (8 × 153 W, measured)
Embodied intensity, I_emb (3-year life) ≈90 gCO₂e/kWh ≈145 gCO₂e/kWh

Hardware Service Life

Published and practitioner assumptions range from 3 to 6 years (Lin et al. 2023; Falk et al. 2026; Lees-Perasso et al. 2026; Ostrouchov et al. 2020). Google applies 6 years uniformly across five TPU generations as an accounting convention (Schneider et al. 2025; Jouppi et al. 2026). The calculation adopts 3 years, with a 3–6 year sensitivity range. A shorter life allocates the same manufacturing emissions across fewer lifetime accelerator kWh, so the choice is conservative; but it is not a measured mean hardware life and will be reviewed as fleet-survival evidence for H100-class and later hardware becomes available. The same life applies to both hardware classes because its evidentiary basis does not vary by accelerator vendor.

Average Accelerator Power

For TPU-served hardware, Google reports measured mean power of 153 W per TPU v6e excluding host over the fleet (Schneider et al. 2025), which gives P̄_acc directly.

For GPU-served hardware, P̄_acc is not observable for any in-scope provider and is expressed as a share of the 5.6 kW eight-accelerator tray TDP. In SAIG benchmarking, mean accelerator power during active serving was 59% of TDP on H200, 52% on B200 and 44% on B300, measured across 388 configurations covering 16 models and batch sizes of 32–384 (Annex B). A published production case study reports GPU utilization rising from 22% to 68% after continuous batching was adopted (Spheron Network 2026). The calculation adopts 40% of TDP, with a 22–68% sensitivity range. This is below measured active-serving power on all three benchmarked classes, which is appropriate for a lifetime average that also includes idle periods. A lower average draw raises I_emb, so the choice is conservative. It is not a measured fleet average and will be reviewed when a provider discloses fleet-level accelerator utilization or lifetime energy per machine.

Survey figures reporting approximately 5% average GPU utilization across general enterprise Kubernetes clusters are not used – these describe general enterprise deployments, not frontier-model serving fleets under continuous cost pressure, and would understate P̄_acc for a population-mismatch reason (rather than due to conservatism).

Table 14: Sensitivity of embodied intensity.
Case GPU-served TPU-served
Central (3 years; 40% of TDP GPU, measured TPU) 90 g/kWh 145 g/kWh
22% of TDP 164 g/kWh —
68% of TDP 53 g/kWh —
100% of TDP, structural floor 36 g/kWh —
6-year life 45 g/kWh 72 g/kWh
HGX B200 baseboard at 1,000 W TDP 110 g/kWh —

The H100 footprint and tray TDP are used for all GPU-served models. Blackwell-class hardware has a higher embodied footprint per tray and would raise GPU embodied intensity by approximately 20%.

8. Data Center Construction

Google’s TPU life-cycle assessment reports data center construction emissions equivalent to approximately 1.9% of location-based operational emissions consistently across five TPU generations, which places the source above the materiality threshold (Schneider et al. 2025). Google amortizes facility construction over 20 years and allocates it in proportion to energy use.

Dividing Google’s reported construction emissions per TPU by the corresponding lifetime facility electricity (measured machine power at Google’s PUE of 1.10 over six years) gives 6.9–7.0 gCO₂e/kWh across all five generations (Schneider et al. 2025). Carbon Trust estimates are lower, principally because they use a 60-year building life; a conversion using Carbon Trust assumptions produces approximately 5.3 gCO₂e/kWh (Carbon Trust 2026). The calculation adopts:

\[k_c=7\ \mathrm{gCO_2e/kWh}=0.007\ \mathrm{kgCO_2e/kWh}\]

The factor is applied after PUE. It is expressed per unit of facility electricity because construction emissions do not vary with grid carbon intensity. It is a cross-provider proxy based on Google facilities, not a site-specific measurement.

9. Model Development

This section allocates a share of provider model-development energy to the customer. It covers development activity that supports the provider’s model portfolio but cannot be assigned to an individual request.

9.1 Development Activity

Model development includes final training runs, post-training and reinforcement learning, experiments and de-risking runs, synthetic-data generation, evaluation, unreleased or failed runs and basic research. Final training runs represent a minority of this compute: Epoch AI estimates final training at 9.6% of OpenAI development compute in 2024, 22.6% for MiniMax and 12.3% for Z.ai (Epoch AI 2025b, 2026b). SemiAnalysis estimates a laboratory-level split of approximately 50% research, 10% final training and 40% serving (SemiAnalysis 2026), meaning that a development term limited to final training would therefore omit most provider development activity.

9.2 Allocation Basis

Provider development energy is allocated according to the customer’s share of provider output, which is measured in tokens and is therefore a physical allocation basis (GHG Protocol 2011; Bashir et al. 2026). Development energy incurred during a reporting period is allocated across output served in the same period.

The calculation does not forecast a model’s lifetime output or amortize an individual training run across future use, which would require assumptions about model lifetime, future demand and total output that providers do not disclose. Period matching also avoids revising earlier reporting periods as lifetime output becomes known. This treatment addresses a corporate inventory; a product-level footprint prepared under a product standard may use a different allocation approach (Bashir et al. 2026).

9.3 Development Ratio

The ratio d is derived from two independent sources; both describe how frontier providers divide accelerator capacity between building models and serving requests, and neither is a direct energy measurement.

Table 15: Evidence supporting the default model-development ratio.
Source Basis d
Epoch AI (2026) Anthropic 2025 compute spending: $4.1bn development compute from press reporting, against $2.7bn serving compute implied by reported revenue of $4.5bn and a 40% gross margin (Epoch AI 2026a) 1.52
SemiAnalysis (2026) Allocation of frontier-lab accelerator capacity: 50% research and experimentation, 10% final training runs, 40% request serving; d = 60 ÷ 40 (SemiAnalysis 2026) 1.50
Applied value 1.5

The two derivations rely on different evidence, a financial reconstruction in the first case and an industry compute allocation in the second. They differ by 0.019, or 1.2% of the lower estimate. The lower value is applied.

The SemiAnalysis allocation implies that final training runs account for 10 ÷ 60, or 16.7%, of development compute, with the remaining 83.3% covering research, failed runs, experimentation and unreleased models. Epoch AI’s separate estimates of 9.6% to 22.6% bracket this value. A method limited to published training-compute figures would capture roughly one sixth of the development activity it is intended to measure.

The result is consistent with Watershed’s framework, which reports training at 32–56% of a model’s total footprint depending on assumptions (Watershed 2026). In the worked example in §10.2, development accounts for 58% of the inventory footprint, slightly above that range, as expected for a boundary that includes research and experimentation as well as training.

ImportantKey finding

The calculation adopts a development-to-serving accelerator-energy ratio of 1.5, a sector-level proxy supported by two independent estimates, not a provider measurement. A provider does not receive a lower development factor solely because it publishes less information.

9.4 Provider Classification

Corporate-level allocation is appropriate only where the provider activity being allocated is sufficiently homogeneous. For providers whose operations substantially comprise development and serving of language models, the sector-level factor applies. Diversified providers require a more granular assessment where evidence permits.

Google’s published 60:40 inference-to-training split for its broader machine-learning fleet is not used as the central factor (Patterson et al. 2022) - although first-party and energy-denominated, it covers a machine-learning estate that includes search, advertising and recommendation systems and is not representative of a frontier-model business line. It is retained as a lower-bound reference.

9.5 Application in the Calculation

The development ratio applies to serving accelerator energy before host and facility uplifts. For GPU-served hardware:

\[\begin{aligned}\text{Serving: }&1.50\times1.10\times1.45=2.39\\\text{Development: }&1.50\times1.45=2.18\end{aligned}\]

The idle uplift does not apply to development energy. It represents serving capacity held ready for inference latency requirements; development workloads are schedulable and are assumed not to require the same reserve.

Development energy is converted to carbon using the serving-region electricity factor because the location of the development compute is not disclosed. This is an explicit simplifying assumption, treated as a systematic uncertainty in §11.2. Embodied IT and construction apply to development activity on the same basis as serving activity.

Where a provider serves a model developed by another organization, including open-weight models, the serving provider’s own development factor applies. Development energy incurred by the original model builder is not allocated where the customer has no transactional relationship or physical allocation basis with that party. Where published training-compute data permit, the excluded quantity is estimated and disclosed.

9.6 Measurement Basis and Direction of Error

Both sources measure the allocation of spending or capacity, not energy. Development workloads generally sustain higher accelerator utilization than serving and are typically contracted on reserved (versus on-demand) terms, so a dollar of development compute likely represents more accelerator-hours and higher average power than a dollar of serving compute. The energy-basis ratio is therefore likely higher than 1.5, and the adopted value is more likely to understate than overstate development emissions. No adjustment is made because the evidence does not quantify the conversion.

An opposing effect applies to embodied emissions. Development hardware likely operates at higher average power than the 40%-of-TDP assumption behind the central GPU embodied factor, so applying that factor to development may overstate development-related embodied emissions. Both effects are disclosed separately and are not netted.

10. Assembled Calculation

Except for reporting-period activity data, factors are fixed and versioned through the factor register.

10.1 Calculation Steps

  1. Serving accelerator energy: \(E_{\mathrm{acc}}=\sum_m [T_{\mathrm{in}}(m)\bar e_{\mathrm{in}}(m)+T_c(m)r(m)\bar e_{\mathrm{in}}(m)+T_{\mathrm{out}}(m)\bar e_{\mathrm{out}}(m)]\).
  2. Development accelerator energy: \(E_{\mathrm{dev}}=\sum_v d(v)E_{\mathrm{acc}}(v)\), with default \(d=1.5\).
  3. Facility energy: \(E_{\mathrm{fac}}=E_{\mathrm{acc}}\times h\times1.10\times1.45+E_{\mathrm{dev}}\times h\times1.45\), where \(h=1.50\) for GPU-served and \(h=1.43\) for TPU-served models.
  4. Operational emissions: \(Op=E_{\mathrm{fac}}\times CI\), recording the provider’s grid-factor rung.
  5. Construction: \(Con=E_{\mathrm{fac}}\times0.007\,\mathrm{kgCO_2e/kWh}\).
  6. Embodied IT: \(Emb=(E_{\mathrm{acc}}+E_{\mathrm{dev}})\times I_{\mathrm{emb}}\), with \(I_{\mathrm{emb}}=0.090\) for GPU-served and \(0.145\,\mathrm{kgCO_2e/kWh}\) for TPU-served models.
  7. Reported emissions: \(Op+Con+Emb\).

Market-based emissions are calculated and reported alongside the location-based result.

10.2 Worked Example

Assume serving accelerator energy of 80.3 MWh, GPU-served hardware, the rung-3 grid factor of 0.41 kgCO₂e/kWh and d = 1.5.

Table 16: Worked example of the assembled inventory calculation.
Term Calculation Result
Development accelerator energy 80.3 MWh × 1.5 120.5 MWh
Facility energy 80.3 × 2.3925 + 120.5 × 2.175 454.2 MWh
Operational emissions, location-based 454.2 MWh × 0.41 kg/kWh 186.2 tCO₂e
Data center construction 454.2 MWh × 7 g/kWh 3.2 tCO₂e
Embodied IT 200.8 MWh × 90 g/kWh 18.1 tCO₂e
Inventory footprint, location-based 207.5 tCO₂e
Of which model development 120.1 tCO₂e
Inference footprint, location-based Serving component only 87.4 tCO₂e
Figure 2: Worked-example emissions shown by inventory boundary and by emission source. The two decompositions are complementary; model development is included within operational, embodied and construction totals.
ImportantKey finding

In the worked example, the inventory footprint is 207.5 tCO₂e, 2.37 times the inference footprint. Model development contributes 120.1 tCO₂e, or 58%. Embodied IT and construction together contribute approximately 10%.

10.3 Boundary Integrity Checks

The following controls prevent double-counting:

  1. CLEER covers accelerator energy only. Host, idle and PUE factors cover separate components.
  2. The idle uplift covers provisioned machines that are not actively serving. CLEER’s utilization treatment applies within active serving.
  3. Host components are IT load and are included before PUE; PUE then scales total IT load to the facility boundary.
  4. NVIDIA’s footprint covers inbound material transport within cradle-to-gate. The §7.2 distribution factor covers finished-hardware shipment from gate to site.
  5. Data center construction applies to post-PUE facility electricity. IT embodied emissions apply to accelerator energy before the operational uplifts.
  6. Development energy is separate from serving energy. d is applied to serving accelerator energy before host and facility conversion.

Per-period inputs comprise token counts by model, the applicable CLEER intensity-table version and the relevant factor, activity-estimate and model-coverage register versions.

10.4 Inference and Inventory Footprints

The calculation produces two related footprints. The inference footprint represents emissions attributable to answering the customer’s requests: the serving component of §§4–8, excluding allocated model development. The inventory footprint adds the customer’s allocated share of provider model development and is the full result of §10.1.

Table 17: Footprint by reporting use.
Use Footprint Basis
Corporate GHG inventory Inventory Includes allocated supplier development activity
Engineering carbon telemetry Inference Represents the effect associated with serving activity
Public model-efficiency comparison Inference Avoids introducing a provider-level development factor unrelated to serving efficiency

Every reported figure identifies whether it is an inference or an inventory footprint. Where the inference footprint is reported, the ratio between the two is provided where relevant; in the worked example, it is 2.37.

11. Uncertainty

The calculation reports a single central estimate. Uncertainty is reported separately and is not incorporated by replacing the central estimate with an upper-bound value. Conservative treatment is applied through factor selection and is not applied a second time by reporting the upper end of the uncertainty range as the result. Uncertainty is treated in two tracks: statistical uncertainty in the CLEER model, and systematic uncertainty from methodological choices, proxies and assumptions.

11.1 Statistical Uncertainty (Track 1)

For model m:

\[u(E_{\mathrm{acc}}(m))=T_{\mathrm{in}}(m)\sigma_{\mathrm{in}}(m)+T_c(m)r(m)\sigma_{\mathrm{in}}(m)+T_{\mathrm{out}}(m)\sigma_{\mathrm{out}}(m)\]

The retained uncertainty represents model-level calibration error, not independent query-to-query variability. Query-level dispersion would decline relative to total activity as volume increases, but calibration error has the same direction across all tokens for a model and scales linearly with volume, so the relative uncertainty σ/ē remains constant.

The correlation between CLEER errors for different models is unknown, since models share calibration sources, donor pools and methodological assumptions. The calculation therefore assumes perfect positive correlation:

\[u(E_{\mathrm{acc}})=\sum_m u(E_{\mathrm{acc}}(m))\]

The resulting range is described as an uncertainty bound, not a confidence interval, and no confidence percentage is assigned. Low, central and high estimates are summed directly across tools; root-sum-square aggregation is not used because it would require an independence assumption the evidence does not support.

Where underlying inputs are materially right-skewed, including relevant §5.6 hardware classes, a symmetric mean ± standard deviation may misrepresent the range. For those cases, the bounds are the 15.87th and 84.13th percentiles, the standard normal quantiles at ±1 standard deviation, applied as a probabilistically symmetric coverage interval (Joint Committee for Guides in Metrology 2008). A moment-matched lognormal approximation may be used where validated against simulation, with its limitations disclosed.

11.2 Systematic Uncertainty (Track 2)

The idle factor, PUE, data center networking treatment, grid carbon intensity, hardware service life, accelerator embodied-carbon factor, model-development ratio and material activity-estimate assumptions are treated as methodological selections rather than random variables. They are reported as discrete scenarios and are not incorporated into the Track 1 distribution. Activity-data scenarios state the share of period activity to which they apply.

The model-development factor carries three principal systematic uncertainties: compute spending is used as a proxy for energy, development energy is assigned the serving-region grid factor, and a sector-level d is used where provider-specific evidence is insufficient. Because d multiplies serving accelerator energy, error in accelerator intensity affects both serving and allocated development. These terms are correlated and are not combined as independent uncertainties.

11.3 Sensitivity Scenarios

The compounded upper bound assumes that several independent factor selections are simultaneously wrong in the same direction – as such, it is a stress case, not an expected outcome.

12. Interpretation and Limitations

The calculation estimates GHG emissions attributable to a customer’s use of third-party generative AI services over a defined reporting period. It combines customer-evidenced activity data, modelled per-token accelerator energy, measured and proxy infrastructure factors, grid or generation carbon-intensity factors, amortized hardware and facility embodied emissions, and an allocated share of provider model-development activity. It produces both location-based and market-based results.

The result is not a direct measurement of request-level emissions, since a customer of a closed model cannot directly observe the energy consumed by an individual request. Material quantities that remain unavailable include actual per-token accelerator energy in the provider’s production fleet, the facility serving a request and its PUE, the carbon intensity of that facility’s electricity, and provider development energy relative to serving energy. Where these quantities are unavailable, the calculation uses measured analogues, modelled estimates, proxies or explicit assumptions according to the hierarchies defined above.

Every such substitution is designed to be replaceable – provider disclosure of a currently unobserved quantity can replace the corresponding estimate without changing the calculation structure.

The calculation, activity estimates and registers are version-controlled together. The uncertainty treatment is reviewed whenever the CLEER intensity table or a Track 2 factor changes. It is also reviewed if model-coverage fallback exceeds 1% of reported emissions.

Annex A. Exclusion Evidence

A.1 Downstream Data Storage

Provider-side storage of data supplied to or generated by an AI service is excluded. Storage controlled by the customer remains within the customer’s existing cloud or IT inventory.

Provider guidance indicates that one token corresponds to approximately 3.5–4 characters of English text (OpenAI 2026; Anthropic 2026). A 2,000-token exchange therefore represents approximately 7–8 kB of UTF-8 text before serialization overhead, rounded to 10 kB as a conservative assumption. Measured constant power of 3.01 W/TB for a 2.0 TB SAS HDD gives 26.4 kWh/TB-year (Nibler and Ropars 2025). A 10 kB exchange retained for one year therefore requires approximately 2.6 × 10⁻⁴ Wh, or approximately 0.11% of Google’s measured 0.24 Wh median text prompt (Google 2025).

The estimate uses dedicated enterprise-drive power over a denser archival tier and the lowest credible per-prompt energy denominator identified in the reviewed literature. Both choices increase the calculated share. The exclusion is reviewed where an in-scope service has multi-year retention with no deletion policy. IEA’s estimate, that storage accounts for approximately 5% of total data center electricity, is not used because it applies across all data center workloads and does not provide a workload-specific allocation for generative AI (International Energy Agency 2025).

A.2 External Network Transmission

Telecommunications infrastructure between the customer and the provider data center is excluded. Networking within the serving data center is addressed in §5.1.

For a 10 kB exchange, a composite network intensity of 0.103 kWh/GB, weighted 90% fixed and 10% mobile access across WAN, FAN and RAN segments, gives 1.0 × 10⁻³ Wh, or approximately 0.43% of a 0.24 Wh prompt (Coroamă 2021). Extrapolated 2025 intensities from the same model give 0.04106 kWh/GB and approximately 0.17% (IO 2026).

The kWh/GB factor is an allocation proxy, not a measurement of marginal network energy. Network infrastructure carries substantial load-independent energy consumption, so the marginal energy of one additional exchange is closer to zero than the factor implies (Mytton et al. 2024). The factor is used only to establish an upper bound supporting the exclusion and does not enter the emissions calculation.

A.3 End-User Devices

Customer employee laptops, displays and peripherals are excluded to prevent double-counting. Their electricity is already included in the customer’s inventory through Scope 2 for on-site use and Scope 3 Category 7 where applicable to remote working (GHG Protocol 2011). For text-based AI interaction, incremental device energy attributable to AI use is not separately identifiable from normal device operation. In-scope services are assumed not to perform material on-device inference; deployment of on-device inference triggers review of this boundary.

A.4 Hardware End-of-Life

Retirement and disposal of provider-owned accelerators are excluded because their estimated GHG contribution is below the materiality threshold.

Table 19: Evidence supporting the treatment of hardware end-of-life.
Source Allocation Finding
Falk et al. A100 LCA No-benefit substitution; no recycling credit Disposal approximately 1.5% of embodied emissions, 2.1 kgCO₂e of 141 kgCO₂e (Falk et al. 2026)
Google TPU LCA Avoided burden assessed but not applied Cascaded use could offset up to 4% of embodied emissions; credit not taken (Schneider et al. 2025)

Embodied emissions represent approximately 8–11% of lifecycle emissions on a location-based basis (Jouppi et al. 2026; Schneider et al. 2025; Mistral AI et al. 2025), so end-of-life contributes approximately 0.12–0.17%. Where embodied emissions reach approximately 25% under market-based accounting, end-of-life contributes approximately 0.38% (Schneider et al. 2025).

The exclusion applies to GHG emissions only – end-of-life can be material for other impact categories, including freshwater ecotoxicity and land use (Falk et al. 2026), which this calculation does not assess.

A.5 Aggregate Cut-Off Test

Table 20: Aggregate quantitative cut-off test, as a share of operational serving emissions.
Source Location-based Market-based
Downstream storage 0.11% 0.11%
Network transmission (2020 intensity) 0.43% 0.43%
End-of-life 0.17% 0.38%
End-user devices Not additive Not additive
Total quantified 0.71% 0.92%

Annex B. SAIG Benchmarking Data Summary Statistics

This annex reports aggregated results from SAIG’s CLEER benchmarking campaign that support §5.1, §5.2 and §7.3. It reports class-level statistics only. Configuration-level data, per-model results and throughput and latency measurements are not published and are available to assurance providers and researchers on request (§B.6).

B.1 Scope and Measurement

The data are a subset of the CLEER benchmarking campaign, which covers more than 2,400 tests across more than 20 open models (Jegham et al. 2026). The subset comprises runs at an input length of approximately 100 tokens with complete power logging.

Table 21: Scope of the benchmarking data used in this calculation.
Accelerator power Host CPU and DRAM power
Instrument NVML, per accelerator RAPL, CPU package and DRAM domains
Hardware H200, B200, B300 Eight-accelerator B300 node
Models 16 open-weight models 4 models
Expert parallelism EP1–EP8 EP8
Batch sizes 32, 64, 128, 256, 384 32, 64, 128, 256, 384
Input length ~100 tokens ~100 tokens
Sample 388 configurations; 1,162 runs 60 runs

Each configuration is the mean of up to three runs with randomized prompt order. Power is averaged over the active serving window, excluding model load and warm-up. The median active window is 5.4 seconds. TDP values used are H200 700 W, B200 1,000 W and B300 1,100 W.

B.2 Accelerator Power During Active Serving

Table 22: Average accelerator power during active serving, as a share of TDP.
Hardware Configurations Models Mean P10 Median P90
H200 115 8 59% 36% 60% 81%
B200 178 13 52% 31% 49% 78%
B300 95 11 44% 27% 43% 62%
All 388 16 52% 31% 50% 77%
Table 23: Mean accelerator power by batch size, as a share of TDP.
Hardware 32 64 128 256 384
H200 48% 49% 57% 67% 72%
B200 44% 46% 54% 58% 60%
B300 38% 41% 43% 48% 52%

Accelerator power rises with batch size on all three classes. No benchmarked class averages 40% of TDP or less during active serving at any batch size except B300 at batch 32.

Table 24: Eight-accelerator configurations.
Hardware Configurations Models Mean power per accelerator Share of TDP
H200 10 2 399 W 57%
B200 30 6 533 W 53%
B300 30 6 486 W 44%

B.3 Host CPU and DRAM Power

Table 25: Host CPU package and DRAM power, eight-accelerator B300 node.
Statistic Value
Runs 60
Mean 375 W
Median 380 W
Standard deviation 13 W
Coefficient of variation 3.6%
P10–P90 352–388 W
Range 349–394 W
CPU packages (two sockets), mean 342 W
DRAM, mean 33 W
Table 26: Mean host CPU and DRAM power by batch size.
Batch size 32 64 128 256 384
Host power 373 W 374 W 374 W 376 W 379 W

Host power varies by less than 2% across the batch range.

B.4 Derived Quantities

Table 27: Host CPU and DRAM multiplier at eight accelerators, h_cd = 1 + 375 W ÷ (8 × P̄_acc).
Hardware At TDP At measured serving power Combined host factor at measured power (× 1.36)
H200 ×1.07 ×1.12 ×1.52
B200 ×1.05 ×1.09 ×1.48
B300 ×1.04 ×1.10 ×1.49

The adopted GPU host factor of ×1.50 (§5.2) lies within the range at measured serving power. The adopted GPU average accelerator power of 40% of TDP (§7.3) lies below mean active-serving power on all three classes.

B.5 Limitations

  • Measurement of benchmark conditions, not real-time production deployment: CLEER benchmarking describes active serving at fixed batch sizes, which are not lifetime averages and do not include idle or provisioned capacity.
  • They measure a single, fixed input length: all runs use an input length of approximately 100 tokens. Longer inputs increase prefill load and would be expected to raise average accelerator power.
  • The host measurement covers one B300 node configuration – applying it to H200 and B200 assumes a comparable dual-socket host.
  • Thin H200 eight-accelerator sample, which is based on 10 configurations across 2 models.
  • Short active windows, with a median of 5.4 seconds. Averages are stable across the three repeats, but short windows are sensitive to transients at the start and end of the window.

B.6 Data Access

The full benchmarking dataset is available to assurance providers and research reviewers on request, subject to a data-use agreement. It includes configuration-level power, throughput and latency by model, hardware, expert parallelism and batch size.

Annex C. Alignment With Existing Frameworks

This annex identifies where the calculation aligns with, or differs from, published accounting and AI-sustainability frameworks. Differences reflect the accounting objective and data available to a corporate consumer of closed-model services, and are disclosed where they affect interpretation.

For an enterprise purchaser of closed-model text services, this calculation is substantially aligned with the relevant accounting boundaries and adds explicit estimation steps where supplier data are unavailable. The assessment below concerns fitness for this use case and transparency of implementation; it does not rank the frameworks or establish the accuracy of proxy factors.

Table 28: Summary of alignment for corporate use of closed AI models.
Framework Relationship to this calculation Added specificity or boundary distinction
GHG Protocol Scope 3 and ICT Sector Guidance Consistent with accounting for purchased services, allocation of supplier emissions, and operational and embodied ICT emissions. Converts model-level token activity into an inventory estimate using documented energy and carbon factors. This comparison does not assert formal conformance.
ITU-T L.1801 Shares a token-based functional unit, lifecycle components, and disclosed cut-off decisions. Focuses on a corporate GHG inventory for purchased text services; L.1801 addresses the broader environmental life cycle of an AI system.
GSF SCI for AI The inference footprint overlaps its consumer-stage, per-token boundary and includes operational and embodied IT emissions. The inventory footprint additionally allocates model development. That combined result is distinct from GSF’s separate consumer and provider SCI scores.
Watershed AI emissions framework Closely aligns on activity-based estimation and coverage of inference, model development, data center overhead, and embodied hardware. Adds CLEER estimates by named closed model, a cached-token treatment, and separate statistical and systematic uncertainty analyses. Provider measurements can replace modeled factors when available.

The detailed comparisons below retain the dimensions and boundary differences behind this assessment. (GHG Protocol 2011; GHG Protocol et al. 2017; ITU-T L.1801 2026; Green Software Foundation 2025; Watershed 2026)

GHG Protocol Scope 3 and ICT Sector Guidance

Table 29: Alignment with GHG Protocol Scope 3 and ICT Sector Guidance.
Dimension This calculation GHG Protocol Scope 3 and ICT Sector Guidance
Boundary Accelerator, host, idle, PUE, model development, embodied IT, distribution and data center construction Purchased services; data center operational and embodied emissions
Functional unit Input, cached and output tokens Per service
Embodied IT Included; 3-year central amortization Included
Model development Included; allocated by output share and reported separately as the inventory–inference difference Not addressed for AI
Grid basis Location-based primary; market-based reported alongside Location-based and market-based
Uncertainty Statistical and systematic tracks; single central result Qualitative

ITU-T L.1801

Table 30: Alignment with ITU-T L.1801.
Dimension This calculation ITU-T L.1801
Boundary Accelerator, host, idle, PUE, model development, embodied IT, distribution and data center construction Full AI-system lifecycle
Functional unit Input, cached and output tokens Per AI system type, including tokens for text generation
Embodied IT Included; 3-year central amortization Included
Model development Included; allocated by output share and reported separately as the inventory–inference difference Reported separately from inference
Grid basis Location-based primary; market-based reported alongside Market-based prioritized
Uncertainty Statistical and systematic tracks; single central result Transparency on sources, assumptions and omissions

GSF SCI for AI

Table 31: Alignment with GSF SCI for AI.
Dimension This calculation GSF SCI for AI
Boundary Accelerator, host, idle, PUE, model development, embodied IT, distribution and data center construction Consumer score: operation and monitoring
Functional unit Input, cached and output tokens Tokens for language models
Embodied IT Included; 3-year central amortization Included
Model development Included; allocated by output share and reported separately as the inventory–inference difference Provider score, outside the consumer score
Grid basis Location-based primary; market-based reported alongside Location-based
Uncertainty Statistical and systematic tracks; single central result —

Watershed AI emissions framework

Table 32: Alignment with Watershed AI emissions framework.
Dimension This calculation Watershed AI emissions framework
Boundary Accelerator, host, idle, PUE, model development, embodied IT, distribution and data center construction Training, inference, data center overhead and embodied hardware
Functional unit Input, cached and output tokens kgCO₂e per million tokens
Embodied IT Included; 3-year central amortization Included
Model development Included; allocated by output share and reported separately as the inventory–inference difference Included
Grid basis Location-based primary; market-based reported alongside —
Uncertainty Statistical and systematic tracks; single central result Tiered by data quality

Sources: (GHG Protocol 2011; GHG Protocol et al. 2017; ITU-T L.1801 2026; Green Software Foundation 2025; Watershed 2026). “—” indicates the dimension is not specified in the published framework summary.

AFNOR Spec 2314 and ISO/IEC TR 20226:2025 provide informative guidance on AI environmental sustainability and were consulted, but do not specify accounting values at this level and are not compared here.

Annex D. Symbols and Units

Energy is expressed in kWh, emissions in kgCO₂e and power in W unless otherwise stated.

Table 33: Symbols and units.
Symbol Quantity §
m Model in the served mix 4
v Provider 9
Tᵢₙ(m), T_c(m), Tₒᵤₜ(m) Uncached input, cached input and output token counts 3
ēᵢₙ(m), ēₒᵤₜ(m) Mean CLEER accelerator energy per input and output token, Wh/token 4
σᵢₙ(m), σₒᵤₜ(m) Standard deviation associated with those means 4, 11
r(m) Cache-read price ratio for model m 4.2
E_acc Serving accelerator energy for the reporting period 4, 10
d Ratio of model-development to serving accelerator energy 9
E_dev Model-development accelerator energy 9, 10
h Host uplift for CPU, DRAM, NICs, storage, fans and PSU losses 5.2
i Idle and provisioned-capacity uplift 5.3
p Power usage effectiveness 5.4
E_fac Facility energy 5, 10
CI Electricity carbon intensity, kgCO₂e/kWh 6
k_c Data center construction intensity, kgCO₂e/kWh of facility electricity 8
M Embodied carbon of a serving machine, kgCO₂e 7
L Hardware service life, years 7
P̄_acc Average accelerator power over installed life 7.3
I_emb Embodied intensity, kgCO₂e/kWh of accelerator energy 7, 10

Annex E. Sources Relied Upon

This register identifies the evidence supporting each input and distinguishes primary measurements, peer-reviewed evidence, standards, modelled studies and corroborating sources. Full references are in the bibliography.

Table 34: Sources relied upon and their principal uses.
Source Key Status Principal use
SAIG, CLEER Technical Report (2026) Jegham et al. (2026) Published methodology Per-token accelerator energy
Google, Measuring the Environmental Impact of Delivering AI at Google Scale (2025) Google (2025) Published first-party fleet telemetry Prompt-energy decomposition; host, idle and PUE evidence
Schneider et al. (Google), Life-Cycle Emissions of AI Hardware (2025) Schneider et al. (2025) Published first-party LCA TPU embodied carbon and power, construction, host share, distribution, end-of-life
Jouppi et al., IEEE Micro (2026) Jouppi et al. (2026) Google-primary TPU amortization convention and lifecycle split
Latif et al. (2025) Latif et al. (2025) Peer-reviewed, physically metered GPU host-power range
Epoch AI, GB200 reference architecture (2025) Epoch AI (2025a) Specification-derived Host and networking corroboration
Choukse et al. (2025) Choukse et al. (2025) Published Server-power boundary
Oviedo et al., Joule (2026) Oviedo et al. (2026) Peer-reviewed Idle, networking and PUE scenarios
NVIDIA DGX H100 specification NVIDIA DGX H100 System Specification (2023) Vendor-primary Host nameplate ceiling
Strubell et al. (2019); Luccioni, Jernite and Strubell (2024) Strubell et al. (2019); Luccioni et al. (2024) Peer-reviewed Accelerator-plus-host boundary precedent
NVIDIA HGX H100 and B200 Product Carbon Footprints (2025) NVIDIA (2025) ISO 14067; critically reviewed GPU embodied carbon
Falk et al. (2026) Falk et al. (2026) Peer-reviewed, independent Embodied carbon, end-of-life, distribution, lifespan
Lees-Perasso et al. (2026), ADEME, Hubblo and Tide Lees-Perasso et al. (2026) Published physical assessment GPU LCA comparison, distribution, lifespan
Mistral AI, Carbone 4 and ADEME (2025) Mistral AI et al. (2025) Standards-conformant LCA Embodied lifecycle share
Li et al. (2025), EcoServe Li et al. (2025) Published bottom-up study Host-tray embodied share
EcoLogits (GenAI Impact and Boavizta) GenAI Impact and Boavizta (2025) Open-source methodology Host-tray embodied share
Schneider Electric, White Paper 99 (2023) Lin et al. (2023) Published lifecycle model Lifespan
Ostrouchov et al. (2020) Ostrouchov et al. (2020) Peer-reviewed GPU survival and lifespan
Spheron Network (2026) Spheron Network (2026) Vendor publication GPU utilization sensitivity range
Carbon Trust (2026) Carbon Trust (2026) Expert-reviewed study Materiality precedent; construction comparison
Watershed (2026) Watershed (2026) Published framework Default PUE; framework alignment; training share
LBNL (2024) Shehabi et al. (2024) Published US PUE series
Uptime Institute (2024) Uptime Institute (2024) Industry survey Global PUE scenario
Cornerstone Sustainability Data Initiative (2026) Cornerstone Sustainability Data Initiative (2026) EPA-method reconstruction Rung-3 generation factor
Argonne National Laboratory, GREET (2025) Argonne National Laboratory (2025) Published LCA model Upstream fuel factors
Guidi et al. (2024) Guidi et al. (2024) Published study Data center grid-intensity comparison
SemiAnalysis, Holbrook et al. (2026) Holbrook et al. (2026) Analyst publication Behind-the-meter technology mix
O’Donoughue et al. (2014) O’Donoughue et al. (2014) Peer-reviewed harmonization Gas lifecycle calibration
Alvarez et al. (2018) Alvarez et al. (2018) Peer-reviewed measurement National methane leakage
Sherwin et al. (2024) Sherwin et al. (2024) Peer-reviewed measurement Aerial leakage sensitivity
Zhang et al. (2020) Zhang et al. (2020) Peer-reviewed measurement Permian leakage sensitivity
EPA, 40 CFR 98 Table C-1; AP-42 US Environmental Protection Agency (2025); US Environmental Protection Agency (2000) Regulatory emission factors Combustion factors
IPCC AR6 WGI Chapter 7 (2021); GHG Protocol GWP values Forster et al. (2021); World Resources Institute and World Business Council for Sustainable Development (2015) Assessment; standard GWP100 values
Climate Power and Cleanview tracker Climate Power and Cleanview (2026) Secondary tracker Behind-the-meter exposure
Nibler and Ropars (2025) Nibler and Ropars (2025) Peer-reviewed Storage power
Coroamă (2021); Green Coding IO (2026); Mytton, Lundén and Malmodin (2024) Coroamă (2021); IO (2026); Mytton et al. (2024) Published; peer-reviewed Network intensity and marginal-energy caveat
OpenAI (2026); Anthropic (2026) OpenAI (2026); Anthropic (2026) Provider documentation Characters per token
IEA (2025), Energy and AI International Energy Agency (2025) Published Storage context
Artificial Analysis (2026) Artificial Analysis (2026) Continuously updated benchmark Cache-read price ratios
Epoch AI (2026), compute expenses Epoch AI (2026a) Published analysis Development-to-serving ratio
Epoch AI (2025, 2026), R&D compute composition Epoch AI (2025b); Epoch AI (2026b) Published analysis Final-training share
SemiAnalysis (2026) SemiAnalysis (2026) Analyst interview Laboratory compute allocation
Bashir et al. (2026) Bashir et al. (2026) Peer-reviewed Corporate versus product allocation
Patterson et al. (2022) Patterson et al. (2022) Google-primary Lower-bound development reference
GHG Protocol Scope 3 Standard (2011); Scope 2 Guidance (2015); ICT Sector Guidance (2017) GHG Protocol (2011); Greenhouse Gas Protocol (2015); GHG Protocol et al. (2017) Published standards Boundary, allocation, electricity accounting
ITU-T L.1801 (2026) ITU-T L.1801 (2026) International Recommendation Cut-off and functional units
GSF SCI for AI (2025) Green Software Foundation (2025) Published specification Framework alignment
Kim, Yoo and Chung (2026) Kim et al. (2026) Peer-reviewed review Evidence of boundary inconsistency
JCGM 101:2008 Joint Committee for Guides in Metrology (2008) International guide Coverage-interval convention

Bibliography

Alvarez, Ramón A. et al. 2018. “Assessment of Methane Emissions from the U.S. Oil and Gas Supply Chain.” Science 361 (6398): 186–88. https://doi.org/10.1126/science.aar7204.
Anthropic. 2026. Glossary. Https://docs.anthropic.com/en/docs/resources/glossary.
Argonne National Laboratory. 2025. GREET: Greenhouse Gases, Regulated Emissions, and Energy Use in Technologies Model. Https://greet.anl.gov/.
Artificial Analysis. 2026. AI Model Pricing: Cache Hit, Input, and Output. Https://artificialanalysis.ai/models#price-cost.
Bashir, Noman et al. 2026. “Amortizing AI Training Carbon Footprint: Challenges, Limitations and a Path Forward.” ACM SIGENERGY Energy Informatics Review. https://www.amazon.science/publications/amortizing-ai-training-carbon-footprint-challenges-limitations-and-a-path-forward.
Carbon Trust. 2026. The Carbon Impact of AI Video Generation. Carbon Trust. https://www.carbontrust.com/our-work-and-impact/guides-reports-and-tools/the-carbon-impact-of-ai-video-generation.
Choukse, Esha et al. 2025. Power Stabilization for AI Training Datacenters. https://arxiv.org/abs/2508.14318.
Climate Power, and Cleanview. 2026. Data Center Air Pollution Tracker. Https://www.cleanview.co/.
Cornerstone Sustainability Data Initiative. 2026. Cornerstone Sustainability Data Initiative: eGRID2024 (2026 Release), Market- and Location-Based. Version 1.1. Zenodo. https://doi.org/10.5281/zenodo.18968658.
Coroamă, Vlad C. 2021. Investigating the Inconsistencies Among Energy and Energy Intensity Estimates of the Internet. Swiss Federal Office of Energy (SFOE).
Epoch AI. 2025a. GB200 Reference Architecture: Server and Rack Power Accounting. Https://epoch.ai/.
Epoch AI. 2025b. Most of OpenAI’s 2024 Compute Went to Experiments. Https://epoch.ai/data-insights/openai-compute-spend.
Epoch AI. 2026a. Compute Accounts for the Majority of Expenses of AI Companies. Https://epoch.ai/data-insights/company-spending-breakdown.
Epoch AI. 2026b. Final Training Runs Account for a Minority of R&D Compute Spending. Https://epoch.ai/gradient-updates/r-and-d-vs-training-compute.
Falk, Sophia, David Ekchajzer, Thibault Pirson, et al. 2026. “More Than Carbon: Cradle-to-Grave Environmental Impacts of GenAI Training on the NVIDIA A100 GPU.” Environmental Impact Assessment Review 121: 108525. https://doi.org/10.1016/j.eiar.2026.108525.
Forster, P., T. Storelvmo, K. Armour, et al. 2021. “The Earth’s Energy Budget, Climate Feedbacks, and Climate Sensitivity.” Chap. 7 in Climate Change 2021: The Physical Science Basis. Contribution of Working Group i to the Sixth Assessment Report of the Intergovernmental Panel on Climate Change, edited by V. Masson-Delmotte, P. Zhai, A. Pirani, et al. Cambridge University Press. https://doi.org/10.1017/9781009157896.009.
GenAI Impact, and Boavizta. 2025. EcoLogits: Estimating the Environmental Impacts of Generative AI. Https://ecologits.ai/.
GHG Protocol. 2011. Corporate Value Chain (Scope 3) Accounting and Reporting Standard. World Resources Institute; WBCSD. https://ghgprotocol.org/corporate-value-chain-scope-3-standard.
GHG Protocol, Global e-Sustainability Initiative, and Carbon Trust. 2017. ICT Sector Guidance Built on the GHG Protocol Product Life Cycle Accounting and Reporting Standard. World Resources Institute; WBCSD. https://ghgprotocol.org/sites/default/files/2023-03/GHGP-ICTSG%20-%20ALL%20Chapters.pdf.
Google. 2025. Measuring the Environmental Impact of Delivering AI at Google Scale. Google. https://services.google.com/fh/files/misc/measuring_the_environmental_impact_of_delivering_ai_at_google_scale.pdf.
Green Software Foundation. 2025. Software Carbon Intensity for Artificial Intelligence (SCI for AI). Https://greensoftware.foundation/standards/sci-ai/.
Greenhouse Gas Protocol. 2015. Scope 2 Guidance: An Amendment to the GHG Protocol Corporate Standard. World Resources Institute and World Business Council for Sustainable Development. https://ghgprotocol.org/scope-2-guidance.
Guidi, Gianluca et al. 2024. Environmental Burden of United States Data Centers in the Artificial Intelligence Era. https://arxiv.org/abs/2411.09786.
Holbrook, Ellie, Robert Boswall, Jeremie Eliahou Ontiveros, Nicolas Bontigui, and Dylan Patel. 2026. What Is so Hard about Behind-the-Meter Power for Datacenters? Part 1: Dumb Science Experiments Vs. Money Printing Machines. SemiAnalysis Newsletter. https://newsletter.semianalysis.com/p/what-is-so-hard-about-behind-the.
International Energy Agency. 2025. Energy and AI. IEA. https://www.iea.org/reports/energy-and-ai.
IO, Green Coding. 2026. “CO2 Formulas.” https://www.green-coding.io/co2-formulas/.
ITU-T L.1801: Guidelines for Assessing the Environmental Impact of Artificial Intelligence Systems. 2026. International Telecommunication Union. https://www.itu.int/rec/T-REC-L.1801-202602-P.
Jegham, Nidhal, Chan Young Koh, Boris Gamazaychikov, and Sasha Luccioni. 2026. CLEER: Closed-Model Latent Energy Estimation Range. Technical Report. Sustainable AI Group. https://reports.sustainableaigroup.com/CLEER-Tech-Report/.
Joint Committee for Guides in Metrology. 2008. Evaluation of Measurement Data – Supplement 1 to the “Guide to the Expression of Uncertainty in Measurement” – Propagation of Distributions Using a Monte Carlo Method. JCGM 101:2008. BIPM. https://www.bipm.org/en/committees/jc/jcgm/publications.
Jouppi, Norman P., Sridhar Lakshmanamurthy, Cliff Young, and David A. Patterson. 2026. “Google’s Training Supercomputers from TPU V2 to Ironwood: Architectural Stability, Scale, Resilience, Power Efficiency, and Sustainability Across Five Generations.” IEEE Micro 46 (4). https://doi.org/10.1109/MM.2026.3699647.
Kim, Min-Kyu, Tae-An Yoo, and Ji-Bum Chung. 2026. “Toward Sustainable AI: A Scoping Review of Carbon Footprint and Environmental Impacts Across Training and Inference Stages.” IEEE Access 14: 18881–96. https://doi.org/10.1109/ACCESS.2026.3659894.
Latif, Imran, Alex C. Newkirk, Matthew R. Carbone, et al. 2025. “Single-Node Power Demand During AI Training: Measurements on an 8-GPU NVIDIA H100 System.” IEEE Access 13: 61740–47. https://doi.org/10.1109/ACCESS.2025.3554728.
Lees-Perasso, Etienne, David Ekchajzer, Gauthier Roussilhe, and Aurélien De Latour. 2026. Analyse de Cycle de Vie de GPU (Cartes Graphiques) Pour l’intelligence Artificielle. ADEME, Hubblo; Tide. https://librairie.ademe.fr/economie-circulaire-et-dechets/9103-analyse-de-cycle-de-vie-de-gpu-cartes-graphiques-pour-l-intelligence-artificielle.html.
Li, Yueying et al. 2025. EcoServe: Designing Carbon-Aware AI Inference Systems. arXiv preprint. https://arxiv.org/abs/2502.05043.
Lin, Paul, Robert Bunger, and Victor Avelar. 2023. Quantifying Data Center Scope 3 GHG Emissions to Prioritize Reduction Efforts. White Paper No. 99. Schneider Electric. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WP99_EN&p_File_Name=WP99_V1_EN.pdf&p_enDocType=White+Paper.
Luccioni, Alexandra Sasha, Yacine Jernite, and Emma Strubell. 2024. “Power Hungry Processing: Watts Driving the Cost of AI Deployment?” Proceedings of the 2024 ACM Conference on Fairness, Accountability, and Transparency (FAccT). https://arxiv.org/abs/2311.16863.
Mistral AI, Carbone 4, and ADEME. 2025. Life Cycle Assessment of a Production AI Model. Mistral AI. https://carbone4.com/en/actualites/ia-generative-mission-mistral-ai.
Mytton, David, Dennis Lundén, and Jens Malmodin. 2024. “Network Energy Use Not Directly Proportional to Data Volume: The Power Model Approach for More Reliable Network Energy Consumption Calculations.” Journal of Industrial Ecology 28 (4): 966–80. https://doi.org/10.1111/jiec.13512.
Nibler, Jakob, and Thomas Ropars. 2025. “Carbon Footprint of Storage in Data Centers: The Impact of Using SSDs for Key-Value Stores.” 2025 IEEE 25th International Symposium on Cluster, Cloud and Internet Computing (CCGrid), 305–14. https://doi.org/10.1109/CCGRID64434.2025.00064.
NVIDIA. 2025. NVIDIA HGX H100 and HGX B200 Product Carbon Footprint Reports. NVIDIA, critical review by WSP. https://images.nvidia.com/aem-dam/Solutions/documents/HGX-H100-PCF-Summary.pdf.
NVIDIA DGX H100 System Specification. 2023. NVIDIA. https://www.nvidia.com/en-us/data-center/dgx-h100/.
O’Donoughue, Patrick R., Garvin A. Heath, Stacey L. Dolan, and Martin Vorum. 2014. “Life Cycle Greenhouse Gas Emissions of Electricity Generated from Conventionally Produced Natural Gas: Systematic Review and Harmonization.” Journal of Industrial Ecology 18 (1): 125–44. https://doi.org/10.1111/jiec.12084.
OpenAI. 2026. Understanding and Counting Tokens. Https://help.openai.com/en/articles/4936856-what-are-tokens-.
Ostrouchov, George, Don Maxwell, Rizwan A. Ashraf, Christian Engelmann, Mallikarjun Shankar, and James H. Rogers. 2020. “GPU Lifetimes on Titan Supercomputer: Survival Analysis and Reliability.” Proceedings of SC20: International Conference for High Performance Computing, Networking, Storage and Analysis. https://sc20.supercomputing.org/proceedings/tech_paper/tech_paper_pages/pap537.html.
Oviedo, Felipe, Fiodar Kazhamiaka, Esha Choukse, et al. 2026. “Energy Use of AI Inference, Efficiency Pathways, and Test-Time Scaling.” Joule, 102430. https://doi.org/10.1016/j.joule.2026.102430.
Patterson, David et al. 2022. Good News about the Carbon Footprint of Machine Learning Training. Google Research Blog; Google Research. https://research.google/blog/good-news-about-the-carbon-footprint-of-machine-learning-training/.
Schneider, Ian et al. 2025. Life-Cycle Emissions of AI Hardware: A Cradle-to-Grave Approach and Generational Trends. arXiv preprint. https://arxiv.org/abs/2502.01671.
SemiAnalysis. 2026. Dylan Patel on AI Compute Allocation (Dwarkesh Podcast Interview). Https://www.dwarkesh.com/p/dylan-patel-3.
Shehabi, Arman et al. 2024. 2024 United States Data Center Energy Usage Report. Lawrence Berkeley National Laboratory. https://eta.lbl.gov/publications/2024-united-states-data-center-energy.
Sherwin, Evan D. et al. 2024. “US Oil and Gas System Emissions from Nearly One Million Aerial Site Measurements.” Nature 627: 328–34. https://doi.org/10.1038/s41586-024-07117-5.
Spheron Network. 2026. “AI Inference Cost Economics in 2026: GPU FinOps Playbook.” https://www.spheron.network/blog/ai-inference-cost-economics-2026/.
Strubell, Emma, Ananya Ganesh, and Andrew McCallum. 2019. “Energy and Policy Considerations for Deep Learning in NLP.” Proceedings of the 57th Annual Meeting of the Association for Computational Linguistics. https://arxiv.org/abs/1906.02243.
Uptime Institute. 2024. Uptime Institute Global Data Center Survey 2024. Https://uptimeinstitute.com/resources/research-and-reports/uptime-institute-global-data-center-survey-results-2024.
US Environmental Protection Agency. 2000. AP-42: Compilation of Air Emissions Factors, Chapter 3: Stationary Internal Combustion Sources. Https://www.epa.gov/air-emissions-factors-and-quantification/ap-42-compilation-air-emissions-factors-stationary-sources.
US Environmental Protection Agency. 2025. 40 CFR Part 98, Subpart C, Table C-1: Default CO2 Emission Factors and High Heat Values for Various Types of Fuel. Https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-98/subpart-C.
Watershed. 2026. An Open Framework for AI Emissions Measurement. Watershed. https://watershed.com/blog/ai-emissions-framework.
World Resources Institute, and World Business Council for Sustainable Development. 2015. Global Warming Potential Values. Standard Guidance. GHG Protocol. https://ghgprotocol.org/sites/default/files/ghgp/Global-Warming-Potential-Values%20%28Feb%2016%202015%29_1.pdf.
Zhang, Yuzhong et al. 2020. “Quantifying Methane Emissions from the Largest Oil-Producing Basin in the United States from Space.” Science Advances 6 (17). https://doi.org/10.1126/sciadv.aaz5120.

Footnotes

  1. Examples of hyperscaler-neocloud exposure evidence: Microsoft Azure, Google Cloud, Amazon Web Services, Meta, Oracle↩︎

  2. LBNL’s series reaches approximately 1.43 in 2023, and its 2024 scenarios range from approximately 1.33 to 1.45 (Shehabi et al. 2024). The adopted value is at the upper end of that range and keeps this calculation directly aligned with Watershed’s framework.↩︎

  3. Every AI provider and hyperscaler has some documented exposure to behind-the-meter gas generation.↩︎